Repository logo
 
Publication

Estudo do Sujamento da Superfície de Transferência de Calor do Evaporador de uma Bomba de Calor aquecido pelo efluente de uma fábrica de pasta para papel

datacite.subject.fosTecnologias de Proteção Ambientalpt_PT
dc.contributor.advisorBeleza, Vitorino de Matos
dc.contributor.authorFernandes, Sofia Assunção
dc.date.accessioned2016-06-08T13:34:43Z
dc.date.available2016-06-08T13:34:43Z
dc.date.issued2010
dc.description.abstractO presente trabalho tem como principal objectivo a avaliação do sujamento da superfície de transferência de calor do evaporador de uma bomba de calor, quando se utiliza o efluente da fábrica de pasta e papel da Portucel Soporcel em Cacia como fluido de aquecimento. Para a realização deste estudo montou-se uma instalação, composta por uma bomba de calor, um circuito de água de arrefecimento do condensador da bomba de calor e um circuito de água residual quente para o aquecimento do evaporador da bomba de calor. O ensaio decorreu durante um período de 84 dias, durante o qual foram registadas as temperaturas em vários pontos dos circuitos e os caudais de circulação. A evolução temporal da quantidade de calor transferida no evaporador, assim como, a comparação do coeficiente global de transferência de calor em condições ideias e experimentais, permitiu verificar que a razão U/U0 para o evaporador da bomba de calor não teve um comportamento decrescente ao longo do período de ensaio, permitindo concluir que, nas condições operatórias da experiência, não ocorreu sujamento na superfície do evaporador. No estudo de corrosão do cobre quando exposto à água residual em questão, obteve-se, para a velocidade de corrosão, o valor de 1,56 mg/(dm2 .dia), indicando assim que a corrosão do cobre naquele meio é praticamente inexistente.pt_PT
dc.description.abstractThis work aims to assess the fouling of the surface of a heat exchanger of a heat pump, when using as heating fluid the effluent of Portucel Soporcel pulp factory, in Cacia. In order to perform this study the experimental apparatus has been set up, being this composed by a heat pump, a water circuit - in order to cool the condenser of the heat pump, as well as a hot wastewater circuit - in order to warm the evaporator of the heat pump. This experiment occurred for an 84-day period, during which they have been recorded temperatures in various points of the circuit, and circulation flows. The temporal evolution of the amount of heat transfer in the evaporator, as well as the comparison of the total coefficient of heat transfer in experimental and ideal conditions, has enabled to verify that the U/U0 ratio in the evaporator of the heat pump has not varied significantly throughout the testing period. This leads to the conclusion that, for this xperiment’s conditions, it did not occur fowling in the evaporator’s surface. As for the corrosion study of copper when exposed to the wastewater, it has been observed a corrosion velocity of 1,56 mg/(dm2 .day), meaning that the copper corrosion in this medium can be neglected.pt_PT
dc.identifier.tid201213877
dc.identifier.urihttp://hdl.handle.net/10400.22/8298
dc.language.isoporpt_PT
dc.subjectSujamentopt_PT
dc.subjectPermutadores de calorpt_PT
dc.subjectBomba de calorpt_PT
dc.subjectEvaporadorpt_PT
dc.subjectCorrosãopt_PT
dc.subjectFoulingpt_PT
dc.subjectHeat exchangerpt_PT
dc.subjectHeat pumppt_PT
dc.subjectEvaporatorpt_PT
dc.subjectCorrosionpt_PT
dc.titleEstudo do Sujamento da Superfície de Transferência de Calor do Evaporador de uma Bomba de Calor aquecido pelo efluente de uma fábrica de pasta para papelpt_PT
dc.typemaster thesis
dspace.entity.typePublication
rcaap.rightsopenAccesspt_PT
rcaap.typemasterThesispt_PT
thesis.degree.nameMestrado em Engenharia Químicapt_PT

Files

Original bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
DM_SofiaFernandes_2010_MEQ.pdf
Size:
815.97 KB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: