Publicação
Estudo de campos eletromagnéticos de baixa frequência em subestações
| datacite.subject.fos | Engenharia e Tecnologia::Engenharia Eletrotécnica, Eletrónica e Informática | |
| datacite.subject.sdg | 09:Indústria, Inovação e Infraestruturas | |
| dc.contributor.advisor | Gomes, António Augusto Araújo | |
| dc.contributor.advisor | Roque, Luís Augusto Correia | |
| dc.contributor.author | TEIXEIRA, RÚBEN PEREIRA | |
| dc.date.accessioned | 2026-09-23T14:39:56Z | |
| dc.date.available | 2026-09-23T14:39:56Z | |
| dc.date.issued | 2026-07-02 | |
| dc.description.abstract | O transporte e a distribuição de energia elétrica através de linhas de muito alta, alta e média tensão, bem como a transformação em subestações e postos de transformação, são processos que originam campos eletromagnéticos de frequência industrial (50 Hz). A avaliação rigorosa destes campos constitui uma exigência da Lei n.º 64/2017, de 7 de agosto, e de diretrizes internacionais aplicáveis, tais como as orientações da Comissão Internacional de Proteção contra Radiações Não Ionizantes. Neste contexto, o presente trabalho centra-se no desenvolvimento de uma metodologia de avaliação de ambientes eletromagnéticos que contribua para garantir a conformidade e a segurança em subestações. O objetivo principal da presente dissertação é analisar o ambiente eletromagnético associado a subestações elétricas de alta e muito alta tensão, avaliando a distribuição espacial do campo eletromagnético e verificando a conformidade com os limites internacionais e nacionais de exposição. Inicialmente, foi realizado um estudo do enquadramento científico, regulamentar e técnico relativo aos campos eletromagnéticos de baixa frequência e às principais fontes de exposição no sistema elétrico. Seguidamente, foi desenvolvido um modelo computacional assente em formulações analíticas, no qual os condutores são representados por troços retilíneos finitos. O cálculo do campo elétrico e magnético é realizado de forma independente, por superposição das contribuições dos condutores, obtendo-se, em cada ponto, as componentes fasoriais e os valores eficazes resultantes. A metodologia de cálculo proposta foi validada através de um caso de referência de uma linha aérea de 500 kV apresentada na norma IEC 62110 e, posteriormente, aplicada a um estudo de caso real de subestação 400/30 kV, com avaliação a uma altura representativa do operador e em secções associadas a vias de circulação e zonas de intervenção. Os resultados permitiram caraterizar os níveis máximos e a contribuição das componentes, apoiando a interpretação física do fenómeno e a identificação de zonas potencialmente mais exigentes para efeitos de segurança e planeamento operacional. | por |
| dc.description.abstract | The transmission and distribution of electrical energy through very high, high and medium voltage lines, as well as its transformation in substations and transformer stations, give rise to industrial-frequency electromagnetic fields (50 Hz). The assessment of these fields is required by Law No. 64/2017, of 7 August, and by applicable international guidelines, such as those issued by the International Commission on Non-Ionizing Radiation Protection. In this context, the present work focuses on the development of a methodology for assessing electromagnetic environments, contributing to compliance verification and safety in substations. The main objective of this thesis is to analyse the electromagnetic environment associated with high and very high voltage substations, assessing the spatial distribution of the electromagnetic field and verifying compliance with national and international exposure limits. Initially, the scientific, regulatory and technical framework related to low-frequency electromagnetic fields was studied, together with the main exposure sources in the electrical system. Subsequently, a computational model based on analytical formulations was developed, representing conductors as finite straight-line segments. The electric and magnetic fields are calculated independently by superimposing segment contributions, yielding phasor components and resulting root mean square values. The proposed calculation methodology was validated using a reference case of a 500 kV overhead line presented in the IEC 62110 standard and was subsequently applied to a real case study of a 400/30 kV substation, with assessment carried out at a representative operator height and along sections associated with circulation routes and intervention areas. The results enabled the characterisation of maximum levels and the contribution of the components, supporting the physical interpretation of the phenomenon and the identification of areas that may be more demanding in terms of safety and operational planning. | eng |
| dc.identifier.tid | 204362121 | |
| dc.identifier.uri | http://hdl.handle.net/10400.22/32856 | |
| dc.language.iso | por | |
| dc.rights.uri | N/A | |
| dc.subject | Electromagnetic field | |
| dc.subject | substation | |
| dc.subject | low frequency | |
| dc.subject | human exposure | |
| dc.subject | safety | |
| dc.subject | Campo eletromagnético | |
| dc.subject | Subestação | |
| dc.subject | Baixa frequência | |
| dc.subject | Exposição humana | |
| dc.subject | Segurança | |
| dc.title | Estudo de campos eletromagnéticos de baixa frequência em subestações | por |
| dc.title.alternative | Study of low-frequency electromagnetic fields in substations | eng |
| dc.type | master thesis | |
| dspace.entity.type | Publication | |
| thesis.degree.name | Mestrado em Engenharia Electrotécnica - Sistemas Eléctricos de Energia |