| dc.description.abstract | As necessidades de aquecimento associadas à manutenção de grandes volumes de água aquecida e temperaturas do ar interior elevadas são as razões maioritárias para os elevados consumos de energia relacionados a complexos desportivos com piscinas interiores. O Clube Propaganda da Natação oferece uma gama extensa de serviços, desde atividades aquáticas dependentes de piscinas interiores assim como aulas de luta corpo-a-corpo, dança e ginásio de musculação. Erros de projeto e deterioração de equipamentos estão entre as causas dos elevados custos de exploração deste clube e de condições interiores da nave de piscinas não ideais. Na tentativa de procurar soluções para resolver estes problemas e com a intenção de reduzir os consumos e consequentes custos, o CPN procurou parceria com a ONGD Engenho & Obra e o ISEP, que, por sua vez, providenciaram a comunicação entre alunos de três especialidades de engenharia na análise do caso de estudo. O CPN apresenta consumos específicos que se enquadram dentro dos valores expectáveis para edifícios portugueses equivalentes, com uma média trianual de 2187 kWh por metro quadrado de área de superfície de plano de água por ano e 518 kWh por metro quadrado de área interna de edifício por ano. Foi delineado o princípio de funcionamento e medições aos principais equipamentos em utilização na procura de anomalias. Realizaram-se também medições às condições internas da nave das piscinas. São exploradas duas soluções de redução de consumos energéticos. A primeira, associada à evaporação, consiste na aplicação de uma cobertura de plano de água, com redução anual de custos prevista compreendida entre os 3840 e 6250 €. A segunda, associada a perdas pela envolvente construtiva, consiste na aplicação de isolamento térmico dos tanques de compensação situados no exterior do edifício, com uma redução anual prevista de 240 €. Foi também modelada uma versão simplificada do edifício em software de simulação energética de edifícios EnergyPlus, na tentativa de quantificar o impacto nos consumos e condições internas da nave da substituição da cobertura da nave de piscinas por uma cobertura com coeficiente de transmissão térmica regulamentar. | pt_PT |
| dc.description.abstract | Heating needs associated with the guarantee of large volumes of warm water and high interior air temperatures are the main reasons for the high energy consumption that is linked with sport complex with indoor pools. Clube Propaganda da Natação (CPN) offers services from aquatic activities dependent of indoor pools as well as close combat and dance classes and a gym. Project mistakes and deterioration of equipment are between the causes of elevated exploration costs of CPN aswell as the non-ideal internal conditions of the swimming pool hall. In an attempt of finding solutions to fixing these problems, and with the intent of reducing the energy consumption e consequent costs, CPN has partnered with Engenho & Obra and ISEP which provided communication between three engineering specialties students in the analysis of case study. CPN presents specific consumption that fits the expectable values for equivalent Portuguese building, with a triennial average of 2187 kWh for each square meter of water plain surface per year and a 518 kWh for each square meter of floor surface of the building per year. The operation principle was delineated and measurements to major equipment in use were done to search for anomalies. Measurements of internal air conditions in the pool area were done as well. Two solutions for the reduction of energy consumption were explored. The first associated with evaporation, consists in the application of an existing water surface cover, with a predicted annual cost reduction between 3480 and 6250€. The second, associated with energy losses through the building construction, consists in the application of external thermal isolation on the compensation tanks found outside of the main building, with a predicted annual cost reduction of 240 €. A simplified version of the building was done in building energy simulation software EnergyPlus, in the attempt of quantifying the impact on the consumption and swimming pool hall internal condition of the substitution of the swimming pool hall roof for a roof with a thermal transmission coefficient that aligns with present regulations | pt_PT |
| dc.identifier.tid | 202549763 | pt_PT |
| dc.identifier.uri | http://hdl.handle.net/10400.22/16771 | |
| dc.language.iso | por | pt_PT |
| dc.subject | Complexos Desportivos | pt_PT |
| dc.subject | Piscinas Interiores | pt_PT |
| dc.subject | Auditoria Energética | pt_PT |
| dc.subject | AVAC | pt_PT |
| dc.subject | Racionalização de Energia | pt_PT |
| dc.subject | Sport Complexes | pt_PT |
| dc.subject | Indoor Pools | pt_PT |
| dc.subject | Energy Audit | pt_PT |
| dc.subject | Energy Rationalization | pt_PT |
| dc.subject | HVAC | pt_PT |
| dc.title | Auditoria Energética e Plano de Racionalização de Consumo e Custo de Energia de um Clube Desportivo | pt_PT |
| dc.type | master thesis | |
| dspace.entity.type | Publication | |
| rcaap.rights | openAccess | pt_PT |
| rcaap.type | masterThesis | pt_PT |
| thesis.degree.name | Mestrado em Engenharia Mecânica - Energia | pt_PT |